Nano Controller: Compressor Management Manual

This manual explains the Compressor Management tab for Nano Controller machines in the Smartlink Mobile app. It focuses only on features available for Nano controllers and gives practical guidance for everyday use, including how to set up the weekly pressure band timer.

What the Compressor Management tab is used for

The Compressor Management tab gives the user direct control over key operating settings of a Nano-controlled compressor. Through this tab, a user can remotely manage machine behavior, adjust pressure-related settings, and define when the compressor should apply different operating profiles.

In practice, this tab is used for three main purposes:

  • Immediate control of the machine through remote start and stop

  • Pressure optimization by defining pressure band profiles that match site demand

  • Automated behavior by applying a weekly schedule to those pressure band profiles

Available features for Nano Controller

Feature

Available on Nano

What it does

Remote start/stop

AVAILABLE

Lets the user start or stop the compressor from the app

Pressure bands

AVAILABLE

Lets the user define pressure control profiles based on machine type

Pressure band schedule

AVAILABLE

Lets the user assign pressure band behavior to times and days of the week

ARAVF

AVAILABLE

Controls whether the machine restarts automatically after voltage failure

Network setup

AVAILABLE

Lets the user configure Wi-Fi or Ethernet connectivity

Remote start and stop

When connected to a Nano Controller, the user can start or stop the compressor directly from the app instead of operating it on the machine itself.

For Nano Controller machines, this action has no special startup limitation. The app and machine can execute the command remotely without the manual-start prerequisite that exists on other controller types.

How to use it

  1. Open the machine in Smartlink Mobile.

  2. Go to the Compressor Management tab.

  3. Select the remote control action.

  4. Choose Start or Stop.

  5. Confirm the action if prompted by the app.

Nano Controller behavior: Remote start/stop is available without additional controller-side constraints.

Pressure bands

Pressure bands define how the compressor should operate within a target pressure range. On Nano Controller machines, users can configure two pressure band profiles. These profiles can then be used directly or through the weekly schedule.

The exact values the user can configure depend on the machine operating principle.

How pressure band logic differs by machine type

Machine type

User-defined values

How the app validates input

Start/Stop

Start value and stop value

The app checks controller-provided minimum and maximum pressure limits and enforces the allowed pressure gap

Load/Unload

Load value and unload value

The app checks controller-provided minimum and maximum pressure limits and enforces the allowed pressure gap

VSD

Setpoint values

The app checks controller-provided minimum and maximum pressure limits and enforces the allowed pressure gap

What to keep in mind

  • The app does not allow arbitrary values.

  • Valid values are limited by controller rules received from the machine.

  • The allowed gap between the lower and upper pressure-related values must remain within controller limits.

  • The profile should match the machine’s operating mode and the customer’s demand pattern.

Weekly timer setup for pressure band scheduling

The Pressure Band Scheduling feature lets the user decide when a compressor should run with a given pressure band profile during the week. This helps align compressor behavior with real site demand, such as production shifts, reduced night usage, or weekend standby operation.

Nano Controller requirements: Weekly scheduling requires a working cloud connection and a correct timezone configuration. If either is incorrect, schedules may not sync correctly or may execute at the wrong local time.

What the weekly timer does

The weekly timer links time slots to predefined pressure band behavior. Instead of manually changing settings every day, the user creates a schedule once and lets the controller apply it automatically.

The app supports:

  • Custom weekly scheduling for different days and time ranges

  • Weekdays quick action to apply the same slot to Monday through Friday

  • Daily quick action to apply the same slot to all seven days

Step-by-step: set up a weekly timer

  1. Open the machine
    In Smartlink Mobile, open the relevant Nano Controller machine.

  2. Go to Compressor Management
    Navigate to the scheduling area for pressure bands.

  3. Open Pressure Band Schedule
    This is where weekly time-based configuration is managed.

  4. Select the day or quick action
    Choose an individual day, or use Weekdays or Daily if the same schedule should be copied broadly.

  5. Add a time slot
    Enter the start time and end time for the period in which a selected pressure band profile should apply.

  6. Assign the intended pressure band behavior
    Select the relevant configured pressure band profile for that time slot.

  7. Repeat as needed
    Add more time slots for additional operating periods during the same day or on other days.

  8. Save and sync
    Save the schedule so the Nano Controller can receive and apply it.

  9. Verify the result
    Review the weekly overview to confirm the correct days, times, and profile assignments are shown.

Common issues to check

  • If the schedule appears correct but activates at the wrong time, verify the timezone.

  • If the schedule does not apply, verify the cloud connection.

  • If expected pressure behavior is missing, verify that the required pressure band profiles were configured and saved first.